PZH R1* is a lightning arrester according to standard EN 61643-11 ed.2 (IEC 61643-11:2011) consisting of multiple non-exhausting spark gaps. Its parameters enable usage in buildings with a considerable level of protection LPL I, such as big industrial complexes and properties of particular importance – hospitals, banks, power plants or buildings with explosion danger. The device is to be installed on the interface of LPZ 0 – LPZ 1 zones according to standard EN 62305 ed.2 (IEC 62305:2010), closest to where the overhead line enters the building i.e. the electric power substation, electrometer or the main distribution boards.
| System configuration TN-C-S | False |
| Nominal discharge surge current (8/20) | 50 kA |
| System configuration DC | False |
| Nominal voltage AC | 400 V |
| Lightning impulse current (10/350 µs) | 50 kA |
| System configuration IT | False |
| System configuration TN | True |
| Max. continuous voltage AC | 440 V |
| System configuration TN-C | False |
| System configuration TN-S | False |
| System configuration TT | False |
| Number of conductors (without earthing) | 1 |
| Voltage protection level | 2,5 kV |